Window energy ratings: U-factor and SHGC (NFRC 100 and NFRC 200)

The structural half of a window submittal gets the attention in South Florida. Design pressure, impact rating, NOA or Florida Product Approval — that is the paperwork that stalls a job. The energy half gets one line on the drawings and almost no scrutiny, right up until the energy reviewer opens the sheet and decides whether the window line you priced is allowed on the project at all.

Two ratings do that work: U-factor and SHGC. They come from different NFRC standards, they read in opposite directions on a data sheet, and in Florida Climate Zone 1 only one of them has a number attached.

Stylized 3D render of a glass window panel on a deep navy background, with lime-green energy beams splitting into two paths — one passing through the glazing, one reflecting off it

The short version

  • U-factor measures how fast heat moves through the whole window assembly — frame, glass, spacer, edge. Rated under NFRC 100. Lower is better.
  • SHGC (solar heat gain coefficient) measures the fraction of solar heat the window admits. Rated under NFRC 200. Lower is better in a cooling-dominated climate.
  • Residential, FBC-EC Table R402.1.2: in Climate Zone 1 the maximum fenestration U-factor is NR — no requirement — while the maximum glazed fenestration SHGC is 0.25. Zone 2 adds a U-factor cap of 0.40 and keeps SHGC at 0.25.
  • Commercial, FBC-EC Table C402.4: Zone 1 caps fixed vertical fenestration at U-0.50 and operable fenestration at U-0.65, with SHGC at 0.25 for south-, east- and west-facing glass and 0.33 for north-facing glass at a projection factor below 0.2.
  • Net effect: SHGC is the number that usually disqualifies a window line, and U-factor is mostly a commercial-glass conversation.

Which counties you are actually designing for

“South Florida” is not a code term. FBC-EC Table R301.1 assigns climate zones by county, and Zone 1A — the hot, humid corner — is Broward, Collier, Hendry, Lee, Miami-Dade, Monroe and Palm Beach. Every other Florida county is 2A.

That distinction is worth money at bid time: Martin and Charlotte County carry a U-factor cap their Zone 1 neighbors do not.

The two ratings, and the third thing the code asks for

Rating Standard What it measures Direction that passes Where Florida sets it
U-factor NFRC 100 Heat conduction through frame, glass, spacer and edge Low Table R402.1.2 (residential), Table C402.4 (commercial)
SHGC NFRC 200 Share of solar heat admitted through the glazing Low Same two tables
VT NFRC 200 Share of visible daylight transmitted High Used as a condition in C402.4.1.1, not as a table maximum

The shape of the Florida table is not arbitrary. In a cooling-dominated climate, heat entering through glass on a summer afternoon dwarfs conduction through the same assembly, so the code puts a hard number on solar gain and none on U-factor. The consequence is concrete: a window line with an unremarkable U-factor but a genuinely low SHGC passes the residential energy review in Miami-Dade, and a line with excellent U-factor and SHGC above 0.25 does not.

The impact-rated exception, and what it does not cover

Table R402.1.2 carries a footnote worth knowing before you disqualify a product. For impact-rated fenestration complying with Section R301.2.1.2 of the Florida Building Code, Residential, or Section 1609.1.2 of the Florida Building Code, Building, the maximum U-factor is 0.65 in Climate Zone 2, against 0.40 for everything else.

Three things about that allowance:

  1. It is a U-factor allowance only. Nothing in the table relieves SHGC — 0.25 still applies to impact glass, and laminated impact assemblies with thicker interlayers do not deliver solar control on their own.
  2. In Zone 1 it is moot, because there is no U-factor requirement to relax.
  3. In Zone 2 it is decisive. A product that fails at U-0.40 can clear at U-0.65 if it is impact-rated and the assembly complies with the referenced section.

So in Broward, Miami-Dade and Palm Beach the energy conversation about a window line is about solar control, while in the Zone 2 counties impact glass buys one extra point of room on U-factor.

Where the number has to come from

FBC-EC Section R303.1.3 (residential) and C303.1.3 (commercial) set the rating method, and it is narrower than most submittals assume:

  • U-factor for windows, doors and skylights is determined under NFRC 100; garage door and rolling door U-factors under NFRC 100 or ANSI/DASMA 105.
  • SHGC and VT of glazed fenestration are determined under NFRC 200.
  • Both are determined by an accredited, independent laboratory and labeled and certified by the manufacturer.
  • Products without a labeled value are assigned a default from the code’s default tables. Those defaults are not competitive with anything a rated window delivers — if the code has to assign the value, the product is already out.

Two traps sit there. A simulation report or a marketing data sheet is not a rating; the value has to be on the label, or on a commercial label certificate specific to that project’s products. And NFRC ratings are issued for a specific product size, so a rating for another size in the same series is not the rating for your opening.

Three details that decide whether the rating applies

1. Orientation and projection factor. Table C402.4 splits SHGC by orientation and projection factor. Section C402.4.3 defines that factor as the horizontal distance from the outermost edge of the overhang or permanently attached shading device to the glazing, divided by the vertical distance from the bottom of the glazing to the underside of that overhang, and each window with a different factor is evaluated separately. “N” means within 45 degrees of true north; everything else is “SEW.” A Zone 1 window with no overhang is held to SHGC 0.25 on its SEW elevations; the same glazing under a deep enough overhang moves into the 0.30 band. Shading is a compliance strategy, not a comfort preference.

2. Area-weighted U-factor. Section C402.4.3.4 permits an area-weighted average U-factor to satisfy the U-factor requirement within each product category in Table C402.4, and products from different categories cannot be combined in that average. It is a U-factor allowance — do not assume it extends to SHGC.

3. Dynamic glazing. Under C402.4.3.3, where dynamic glazing is used to satisfy the table, the ratio of the higher to the lower labeled SHGC must be at least 2.4 and the glazing must be automatically controlled to modulate solar gain in multiple steps. It is evaluated separately and cannot be area-weighted with non-dynamic glazing; if both labeled values already comply, the section does not apply.

One more for replacement work: Section C401.2.2 requires a replacement unit to meet Table C402.4 on both U-factor and SHGC, with an area-weighted U-factor exception per product category.

The energy review is not the structural review

Air leakage is a separate line in the same chapter — R402.4.3 for residential (windows, skylights and sliding glass doors at 0.3 cfm per square foot, tested under NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440) and Table C402.5.2 for commercial (0.20 cfm per square foot for windows). We covered that track in water infiltration and air leakage ratings.

The structural path runs on different documents entirely: impact testing, design pressure, and the approval that has to cover both. A window can be fully approved structurally and still fail the energy sheet, because the NOA answers a pressure question and the NFRC label answers a heat-flow question. See NOA vs. Florida Product Approval for which approval applies where.

Residential projects carry one more artifact: the Energy Performance Level display card, required by FBC-EC Section R401.3 and by Florida Statute 553.9085 as an addendum to each sales contract. The builder certifies that installed efficiencies match the plans, which makes the SHGC on the label a field-verifiable number rather than a design-phase one.

The 9th Edition moves this spec again

The FBC 9th Edition takes effect December 31, 2026 and pulls Florida’s energy chapter toward the 2024 IECC. The values that clear today are version-specific, and the permit date decides the version — the same rule that governs the wind-load standard, so verify against the edition that will govern the permit rather than the one you priced under. See what changes on December 31.

Three checks before you price a window line

  1. Get the climate zone from Table R301.1 by county, not from the phrase “South Florida.” Zone 1A is a specific list, and Zone 2 has a U-factor cap Zone 1 does not.
  2. Pull U-factor and SHGC from the label or project label certificate, confirm the entry in the NFRC directory, and check the size and configuration.
  3. Check SHGC per elevation. Orientation and overhang depth change the number the code applies to that opening.

Those three checks take an afternoon and remove the most common reason an energy sheet comes back after the glass is ordered — the same discipline we run on every compliance package: know which number governs the opening, then price against it.